- Room: 8 m × 6 m × 3 m; volume 144 m³.
- Gross wall area: 84 m²; assumed window area: 12 m².
-
Opaque wall conductance:
72 / Rwall W/K.
-
Separate window, roof, and floor conductances are fixed at
12/0.35, 48/2.2, and 48/2.5 W/K respectively.
-
Ventilation conductance:
ρcp · V · ACH / 3600,
with ρcp = 1200 J/(m³K).
-
Effective heat capacity: 180 kJ/K. No moisture, thermal mass,
infiltration distribution, or thermal bridges are modeled.
-
Fixed internal/solar gain proxy: 300 W. No day/night cycle is
simulated.
-
Ideal 100%-efficient electric heater with a proportional-integral
controller. No cooling is modeled.
C dT/dt = Qheater + Qgains
− UAenv(Tin − Tout) − UAvent(Tin − Tout)
UAenv = 72/Rwall + 12/0.35 + 48/2.2 + 48/2.5
UAvent = 1200 × 144 × ACH / 3600